Deluxia Palace, Barbaros Mah. Mor Sümbül Sok. No:5A/88 Kat:3, Ataşehir / İstanbul info@uztherm.com

F152 flame monitoring device

SIL3 evaluation unit for optical flame monitoring with an FFS07 or FFS08 UV/IR sensor, approved for continuous operation

Flame monitoring

LAMTEC · F152

  • SIL3
  • UV · IR (FFS07 / FFS08)
  • Continuous
  • 10 … 200 Hz

Paired with an FFS07 or FFS08 flame sensor, F152 forms a safety arrangement that optically watches the flames of single-burner systems, for applications that do not call for demanding flame discrimination. It works only with these two sensors, and each F152 takes a single sensor. The sensors measure in the UV or IR range, which is chosen to suit the fuel. F152 is approved for continuous operation and certified to SIL3 under DIN EN 61508-2.

The unit has a plastic housing with integrated control electronics and mounts on a DIN rail. Thanks to its two-channel design with electronic self-monitoring, no mechanical shutter is needed. It evaluates the flame frequency digitally between 10 and 200 Hz, shows its states on LEDs and has a 0…20 mA intensity output as standard. No adaptation to national mains frequencies is required. The status contact (NC) and the flame signal contact (NO) are floating changeover contacts.

F152 serves single- or multi-fuel burners in heating plants, power plants, process furnaces and standard boiler applications, firing oil, gas, biomass, dust or process gases. The standard supply voltage is 230 V AC; a 115 V AC version is prepared at the factory on request. It fulfils DIN EN 298 and, for process burners, DIN EN 746-2.

F152 flame monitoring device
F152 flame monitoring device 1F152 flame monitoring device 2F152 flame monitoring device 3
Benefits

F152 flame monitoring device

  • Optical flame monitoring in the UV or IR range with an FFS07 or FFS08 sensor
  • Approved for continuous operation; SIL3 to DIN EN 61508-2
  • Digital evaluation of the flame frequency between 10 and 200 Hz
  • Two-channel design with electronic self-monitoring, so no mechanical shutter is needed
  • 0…20 mA intensity output as standard and LED status indication
  • DIN-rail module that needs no adaptation to national mains frequencies
  • EU type examination certificates to (EU) 2016/426 and 2014/68/EU, UL 60730-2-5 and IACS UR E10 ship certification
F152

Key specifications

SpecificationF152
Flame detectionUV · IR (FFS07 / FFS08)
Operating modeContinuous
Flame frequency evaluation10 … 200 Hz
Analogue outputs0 … 20 mA (flame intensity)
Supply voltage230 V AC +10/-15 % · 115 V AC +10/-15 %
Power consumption≤ 5 VA
Degree of protectionIP20
Ambient temperature-10 … +60 °C
Safety integrity levelSIL3

Full technical data: data sheet(opens in a new tab)

Approvals and standards

  • CE declaration of conformity (2014/35/EU, 2014/30/EU, 2014/68/EU, (EU) 2016/426, 2011/65/EU, 2015/863/EU)
  • EU type examination certificate — 2014/68/EU, Module B (pressure equipment)
  • EU type examination certificate — (EU) 2016/426 (gas appliances)
  • SIL3 — DIN EN 61508
  • DIN EN 298
  • DIN EN 13611
  • DIN EN 60730-2-5
  • DIN EN 60730-1
  • UL 60730-2-5 (US)
  • Ship certification — IACS UR E10 Rev. 8
  • UKCA marking (United Kingdom)

Documents

Let's choose the right product for your project together

Tell us about your plant and what you need, and our engineers will recommend the right solution.