Deluxia Palace, Barbaros Mah. Mor Sümbül Sok. No:5A/88 Kat:3, Ataşehir / İstanbul info@uztherm.com

F120I flame monitoring device

SIL3 DIN-rail device that supervises gas flames by ionisation, using a 390 V auxiliary voltage

Flame monitoring

LAMTEC · F120I

  • SIL3
  • Ionisation · 390 V
  • Intermittent · Continuous
  • -20 … +70 °C

F120I is a safety device that supervises pilot and main flames of gaseous fuels by ionisation; LAMTEC developed it from its F130I. In both intermittent and continuous operation it applies a 390 V ionisation auxiliary voltage. This measuring method lets each flame be watched on its own in single- and multi-burner systems. It is aimed at power stations, the chemical industry and industrial firing plants that need a flame monitor meeting SIL3.

The control electronics are built into the housing, and the device is mounted on a DIN rail in the control cabinet. Its two-channel design checks itself electronically, LEDs show the status, and it needs no adaptation to national mains frequencies. Both single- and two-electrode operation are supported. For the flame failure detection time (FFDT), values of 1 s, 3 s and 5 s are given, and the permitted ambient temperature is -20…+70 °C.

Outputs: digital signals for status and flame, a relay contact for the flame signal, open-collector outputs for flame ON and standby, and analogue outputs for ionisation voltage and flame intensity (4…20 mA). F120I is not meant to close fuel valves directly: the signal from its safe output contact has to be processed further in the plant's higher-level control system. It is supplied from the factory for 230 V AC or 115 V AC.

F120I flame monitoring device
F120I flame monitoring device 1F120I flame monitoring device 2
Benefits

F120I flame monitoring device

  • Ionisation supervision of pilot and main flames on gaseous fuels, in intermittent and continuous operation
  • 390 V ionisation auxiliary voltage; single- and two-electrode operation
  • Each flame watched on its own in single- and multi-burner systems
  • SIL3 to DIN EN 61508; EU type examination certificates to 2014/68/EU and (EU) 2016/426
  • Two-channel design with electronic self-monitoring, as a module for DIN-rail mounting
  • 4…20 mA flame intensity output, open-collector outputs and an LED intensity display
  • Fulfils DIN EN 298 and, for process plants, DIN EN 746-2
  • Works on any national mains frequency without adjustment
F120I

Key specifications

SpecificationF120I
Flame detectionIonisation
Operating modeIntermittent · Continuous
Ionisation auxiliary voltage390 V
Flame failure detection time (FFDT)1 s · 3 s · 5 s
Supply voltage230 V AC · 115 V AC
Analogue outputs4 … 20 mA (flame intensity) · ionisation voltage
Ambient temperature-20 … +70 °C
Safety integrity levelSIL3

Full technical data: data sheet(opens in a new tab)

Approvals and standards

  • CE declaration of conformity (2014/35/EU, 2014/30/EU, 2014/68/EU, (EU) 2016/426, 2011/65/EU, 2015/863/EU)
  • EU type examination certificate — 2014/68/EU, Module B (pressure equipment)
  • EU type examination certificate — (EU) 2016/426 (gas appliances)
  • SIL3 — DIN EN 61508
  • DIN EN 298
  • DIN EN 13611
  • DIN EN 50156-1
  • DIN EN 50156-2
  • DIN EN 60730-2-5
  • DIN EN 60730-1

Documents