F200K Ex explosion-protected compact flame scanner
SIL3 compact flame scanner for hazardous areas: F200K Ex for Ex zones 1 and 21, F200K Ex-II for zones 2 and 22
LAMTEC · F200K Ex · F200K Ex-II
- Ex 1/21 · Ex 2/22
- SIL3 · Continuous
- UV-2 · IR-1
F200K Ex and F200K Ex-II are the Ex versions of the F200K compact flame scanner, designed for potentially explosive atmospheres. The flame sensor and the switching amplifier share one housing, so no separate evaluation unit is needed. The scanner supervises the flame in continuous operation on firing systems with one or more burners and is certified to SIL3 under DIN EN 61508-2. The Ex design opens F200K up to further uses, above all in the chemical and petrochemical industry. F200K Ex is marked for Ex zones 1 and 21, F200K Ex-II for Ex zones 2 and 22.
Both models are available with a UV-2 (210–380 nm) or an IR-1 (1200–2800 nm) sensor. UV-2 is preferred for oil, gas and special gases like refinery gas, blast furnace gas and hydrogen; IR-1 for oil, gas, wood and coal firing with heavy flue gas recirculation, and for yellowish waste gases that emit no UV or whose UV part is screened by water vapour and dust. Sensitivity is set in several stages and the flame frequency is evaluated digitally; the two-channel design monitors itself electronically. The supply is 24 V DC ± 20 %, power consumption is up to 4 W and the analogue output is 0/4…20 mA.
F200K Ex has a nickel-plated, varnished aluminium housing rated IP66; it operates at ambient temperatures of -40…+65 °C with the UV-2 sensor and -40…+60 °C with IR-1, and it mounts only on threaded FV30 or FV40 brackets. F200K Ex-II is rated IP66/67, operates at -40…+75 °C with UV-2 and -40…+60 °C with IR-1, and mounts on threaded FV30/FV40 or plug-in FH30/FH40 brackets. The FS50 cooling air housing can be used with F200K Ex-II, while no cooling air housing is offered for Ex zone 1. On F200K Ex-II, the 3 m connecting cable can be extended by up to 250 m at a 20.5 V supply. A UV-6 FO fibre-optic sensor variant is also available for F200K Ex-II in Ex zone 2.
F200K Ex explosion-protected compact flame scanner
- F200K Ex for Ex zones 1 and 21, F200K Ex-II for Ex zones 2 and 22
- Flame sensor and switching amplifier in one compact housing; no separate evaluation unit
- Continuous operation on single- and multi-burner systems; SIL3 to DIN EN 61508-2
- Ex design especially suited to chemical and petrochemical applications; UV-2 or IR-1 sensor
- Multi-stage sensitivity setting and digital flame frequency evaluation
- LED status display and a connectable trend display for aligning the scanner on the flame
- Two-channel system with electronic self-monitoring
- EU type examination certificates (2014/68/EU, (EU) 2016/426), IEC 60079 Ex zone 1 certificate for F200K Ex, Ex zone 2 for F200K Ex-II, UL 372 and CSA C22.2 No. 199
Key specifications
| Specification | F200K Ex | F200K Ex-II |
|---|---|---|
| Flame detection | UV-2 210 … 380 nm · IR-1 1200 … 2800 nm | UV-2 210 … 380 nm · IR-1 1200 … 2800 nm |
| Operating mode | Continuous | Continuous |
| Supply voltage | 24 V DC ± 20 % | 24 V DC ± 20 % |
| Power consumption | ≤ 4 W | ≤ 4 W |
| Analogue outputs | 0/4 … 20 mA, load 200 Ω | 0/4 … 20 mA, load 200 Ω |
| Explosion protection (Ex) | Ex zones 1 and 21 · II 2G Ex db IIC T6…T5 Gb · II 2D Ex tb IIIC T80 °C, T95 °C Db | Ex zones 2 and 22 · II 3G Ex nA nC IIC T6…T5 Gc X · II 3D Ex tc IIIC T85 °C Dc X |
| Degree of protection | IP66 | IP66/67 |
| Ambient temperature | -40 … +65 °C (UV-2) · -40 … +60 °C (IR-1) | -40 … +75 °C (UV-2) · -40 … +60 °C (IR-1) |
| Safety integrity level | SIL3 | SIL3 |
Approvals and standards
- CE declaration of conformity (2014/35/EU, 2014/30/EU, 2014/68/EU, (EU) 2016/426, 2011/65/EU, 2015/863/EU)
- EU type examination certificate — 2014/68/EU, Module B (pressure equipment)
- EU type examination certificate — (EU) 2016/426 (gas appliances)
- SIL3 — DIN EN 61508
- DIN EN 298
- DIN EN 13611
- DIN EN 50156-1
- DIN EN 60730-2-5
- DIN EN 60730-1
- UL 372 (US)
- CSA C22.2 No. 199 (CA)
- Ex zone 1 — IEC 60079-0, -1, -7, -11, -28, -31 (F200K Ex)
- Ex zone 2 — IEC 60079-0, -7, -15, -31 (F200K Ex-II)
- ANSI/ISA-12.12.01-2015 — Class I, Division 2 hazardous locations (US)
- CSA C22.2 No. 213-15 — Class I, Division 2 hazardous locations (CA)
Accessories
- Threaded FV30 and FV40 brackets, including types with purge air connection and globe joint
- FG24 Ex-II junction box (F200K Ex-II, Ex zone 2): marked II 3G, IP66, four screwed cable glands
- FFP30 testing device: simulates a varying flame frequency and screws onto the scanner, which must be set sensitive enough to detect the simulation
More products in this group
F120I flame monitoring device
SIL3 DIN-rail device that supervises gas flames by ionisation, using a 390 V auxiliary voltage
- SIL3
- Ionisation · 390 V
- Intermittent · Continuous
F130I flame monitoring device
SIL3 flame monitor with ionisation, UV tube and LDR inputs, approved for continuous operation with ionisation
- SIL3
- Ionisation · UV · LDR
- Continuous (ionisation only)
F152 flame monitoring device
SIL3 evaluation unit for optical flame monitoring with an FFS07 or FFS08 UV/IR sensor, approved for continuous operation
- SIL3
- UV · IR (FFS07 / FFS08)
- Continuous
F200K compact flame scanner
SIL3 compact flame scanner with a UV or IR sensor and evaluation electronics in one housing, for continuous operation
- SIL3 · IP67
- UV-2 · IR-1 · IR-2
- 24 V DC
Let's choose the right product for your project together
Tell us about your plant and what you need, and our engineers will recommend the right solution.