Deluxia Palace, Barbaros Mah. Mor Sümbül Sok. No:5A/88 Kat:3, Ataşehir / İstanbul info@uztherm.com

F300K compact flame scanner

SIL3 compact flame scanner with a UV, IR or dual UV/IR sensor and three operating modes; standard version for Ex zone 2

Flame monitoring

LAMTEC · F300K

  • SIL3 · Ex zone 2
  • UV · IR · UVIR-1
  • -40 … +85 °C
  • IP66/67

F300K is a compact flame scanner that houses the evaluation unit and flame sensor in a single device, with sensor, amplifier and flame relay all built in. It was developed for complex industrial firing systems and is used on plants with or without flame discrimination tasks, on single and combination burners, for combustion chamber monitoring, in power and heating plants, process furnaces and waste incineration plants, and wherever the view of the flame is restricted. The standard version is certified for Ex zone 2, and a version for Class I, Division 2 (Groups A, B, C, D) hazardous locations is also offered.

The scanner analyses the flame digitally in both the UV and the IR range and comes with a single sensor or a dual UV/IR sensor. UV-4 and UV-4.6 detect in the 215–360 nm band and IR-4 in 1000–2200 nm; the UVIR-1 dual sensor covers 215–360 nm in the UV and 850–1700 nm in the IR, and it is meant for demanding duties such as multi-burner plants with different fuels or strong background radiation. Three preselectable operating modes apply their own detection parameters to different fuels and operating conditions and can be changed during operation. A self-learning flame ON/OFF function and 14 frequency ranges between 5 and 210 Hz are provided.

The LED version shows flame status, operating mode and intensity, while the version with an integrated graphical interface is set up entirely through menus. The version without an integrated interface has to be operated with a graphical user interface or the F300K remote software. The 0/4…20 mA output can be assigned to flame intensity or to the RMS value of the sensor signal. Up to 32 scanners can be linked to a PC over the FSB bus; a repeater is needed once the total line exceeds 80 m. A cooling air housing allows temperatures above +85 °C, and the F300K-FO fibre optic system serves boilers with a restricted flame view at up to 350 °C.

F300K compact flame scanner
F300K compact flame scanner 1F300K compact flame scanner 2F300K compact flame scanner 3F300K compact flame scanner 4F300K compact flame scanner 5
Benefits

F300K compact flame scanner

  • Evaluation unit and flame sensor in one compact device; standard version certified for Ex zone 2
  • Single sensor or dual UV/IR sensor; digital flame analysis in the UV and IR range
  • Three preselectable operating modes for different fuels and operating conditions
  • Self-learning flame ON/OFF function and menu-guided commissioning
  • 0/4…20 mA output for flame intensity or RMS value; LED version or version with an integrated graphical interface
  • FSB bus; PROFIBUS, Modbus TCP, Modbus RTU, Ethernet and CANopen through the FSB gateway
  • Class I, Division 2 version; SIL3 to DIN EN 61508 parts 1–7
  • IP66/67 protection and an operating temperature of -40…+85 °C
F300K

Key specifications

SpecificationF300K
Flame detectionUV-4 · UV-4.6 · IR-2 F · IR-4 · UVIR-1
Operating modeContinuous
Supply voltage24 V DC ± 20 %
Analogue outputs0/4 … 20 mA, load ≤ 240 Ω
InterfacesFSB · PROFIBUS, Modbus TCP, Modbus RTU, Ethernet (Frame), CANopen (FSB-Gateway, optional)
Explosion protection (Ex)Ex zone 2 · Ex nA nC ic IIC T5 (T6) Gc X
Degree of protectionIP66/67
Ambient temperature-40 … +85 °C
Cable length≤ 200 m
Safety integrity levelSIL3

Full technical data: data sheet(opens in a new tab)

Approvals and standards

  • CE declaration of conformity (2014/35/EU, 2014/30/EU, 2014/68/EU, (EU) 2016/426, 2011/65/EU, 2015/863/EU)
  • EU type examination certificate — 2014/68/EU, Module B (pressure equipment)
  • EU type examination certificate — (EU) 2016/426 (gas appliances)
  • SIL3 — DIN EN 61508
  • DIN EN 298
  • DIN EN 13611
  • DIN EN 50156-1
  • DIN EN 50156-2
  • DIN EN 60730-2-5
  • DIN EN 60730-1
  • CSA C22.2 No. 199 (CA)
  • Ex zone 2 — IEC 60079-0, -7, -11, -15, -31
  • ANSI/ISA-12.12.01-2015 — Class I, Division 2 hazardous locations (US)
  • CSA C22.2 No. 213-15 — Class I, Division 2 hazardous locations (CA)

Accessories

  • Flamescanner Remote Software: links to a PC through an FSB/USB module and adapter cables, sets every parameter, and records and analyses data
  • FB30 external user interface with the functions of the integrated one: portable FB30-00 or panel-mounted FB30-10, IP67; powered from the F300K 24 V DC supply
  • Connecting cables in 3, 5 and 10 m: standard LiYCY or silicone; for special ambient conditions, silicone cable in a stainless steel protective tube
  • Threaded FV30 and FV40 brackets, including types with purge air connection, with globe joint and FV30-15 / FV40-15 for a boiler pressure of 4 bar
  • FK41 cooling air housing, fitted with a purge air coupling and a globe joint, for running F300K at higher ambient temperatures
  • Power supplies: FN30-00 (IP20) and FN30-10 (IP66) for 100–240 V; FN20 with relay output (IP20) and FN30-20 (IP66) for 230/115 V
  • FFP30 flame scanner testing device: simulates UV and IR flames in four changing frequency ranges, screws onto F300K and runs on a 9 V battery