Actuator for Ex zone 1
ATEX/IECEx-certified actuator for Ex zone 1 with five torque options from 6 to 50 Nm, for ETAMATIC, FMS and VMS
LAMTEC · 662R2140 · 662R2141
- Ex zone 1 · ATEX · IECEx
- 6 / 20 / 30 / 40 / 50 Nm
- IP65
- ETAMATIC · FMS · VMS
In areas classified as Ex zone 1, this LAMTEC actuator operates the dampers and valves of firing plants. Type 662R2140 has a die-cast aluminium housing and type 662R2141 a stainless steel housing; both are offered with torques of 6, 20, 30, 40 and 50 Nm. The ATEX version is marked II 2G Ex d IIC T6 Gb (IBExU 12ATEX1096 X) and works at ambient temperatures of -20…+60 °C; the IECEx version is marked Ex d IIC T6 Gb (IECEx IBE 14.0056X) and is limited to -20…+40 °C. The actuator is TÜV-approved for use with ETAMATIC, FMS and VMS; use with CMS requires an individual approval.
The standard version runs on 230 V AC / 50 Hz, is operated by three-point step control and completes a 90° movement in 60 seconds. Order options include 115 V AC or 230 V AC supply at 50 or 60 Hz, running times of 30 or 40 seconds and angular displacements of 120°, 135°, 180° or 270°. Position is reported by a TÜV-approved 5 kΩ conductive-plastic potentiometer, coupled positively and without backlash. Two limit switches and two additional switches are fitted; the three-point step version is supplied only with electric manual override.
Optional integrated electronic control drives the actuator with a 4…20 mA signal; this version reports its position as 4…20 mA and is supplied without manual override. With ETAMATIC, FMS or VMS, that feedback does not count as a fail-safe position indication, so an additional TÜV-approved 5 kΩ conductive-plastic potentiometer is mandatory. The shaft measures Ø12 × 25 mm (Ø12 × 30 mm with the stainless steel housing) and has a 4 × 4 × 14 mm feather key; mounting uses 4 × M6 on a Ø 50 mm hole circle. A coupling or lever is not included and has to be ordered on its own.
Actuator for Ex zone 1
- ATEX or IECEx certified versions for Ex zone 1 (Ex d IIC T6 Gb)
- Torque options of 6, 20, 30, 40 and 50 Nm
- Die-cast aluminium or stainless steel housing, degree of protection IP65
- TÜV approval for use with ETAMATIC, FMS and VMS
- Position feedback via a TÜV-approved 5 kΩ conductive-plastic potentiometer
- Optional integrated electronic control for operation with a 4…20 mA signal
- Two limit switches and two additional switches
- Cable glands: 1 × M16 × 1.5 (cable Ø 3.5–8.5 mm) and 1 × M20 × 1.5 (cable Ø 11–14.2 mm)
Key specifications
| Specification | 662R2140 | 662R2141 |
|---|---|---|
| Torque | 6 / 20 / 30 / 40 / 50 Nm | 6 / 20 / 30 / 40 / 50 Nm |
| Running time (90°) | 60 s (standard version) · 30 / 40 s (optional) | 60 s (standard version) · 30 / 40 s (optional) |
| Supply voltage | 115 / 230 V AC · 50 / 60 Hz (230 V AC / 50 Hz standard version) | 115 / 230 V AC · 50 / 60 Hz (230 V AC / 50 Hz standard version) |
| Control | 3-point step · 4 … 20 mA (optional) | 3-point step · 4 … 20 mA (optional) |
| Position feedback | 5 kΩ potentiometer (conductive plastic) · 4 … 20 mA (with electronic control) | 5 kΩ potentiometer (conductive plastic) · 4 … 20 mA (with electronic control) |
| Explosion protection (Ex) | Ex zone 1 · ATEX: II 2G Ex d IIC T6 Gb · IECEx: Ex d IIC T6 Gb | Ex zone 1 · ATEX: II 2G Ex d IIC T6 Gb · IECEx: Ex d IIC T6 Gb |
| Degree of protection | IP65 | IP65 |
| Ambient temperature | ATEX: -20 … +60 °C · IECEx: -20 … +40 °C | ATEX: -20 … +60 °C · IECEx: -20 … +40 °C |
| Material | Die-cast aluminium | Stainless steel |
| Weight | 8 kg | 11.6 kg |
Approvals and standards
- CE declaration of conformity (2014/35/EU, 2014/30/EU, 2011/65/EU)
- DIN EN 60730-1
- Ex zone 1 — EN 60079-0, -1 (IBExU 12ATEX1096 X, IECEx IBE 14.0056X)
- TÜV approval (for use with ETAMATIC, FMS and VMS)
Documents
More products in this group
CMS combustion management system
Modular burner and plant control that scales from small industrial burners to large installations
- SIL3 · CE · UL
- ≤ 10 actuators
- Modbus TCP
BT300 burner control unit
Compact burner-mounted unit that pairs fuel-air ratio control with a burner sequencer
- ≤ 3 actuators
- Burner-mounted
- SIL3 (BT331, BT341)
MCC-BC400 burner sequencer
Configurable burner sequencer for gas-fired, oil-fired and dual-fuel burners
- SIL3 · CE · UL
- Gas · Oil · Dual fuel
- Modbus TCP
BC300 gas burner sequencer
Burner sequencer for industrial gas burners in thermal process plants, approved for intermittent and continuous operation
- SIL3 · CE
- Intermittent · Continuous
- High-temperature operation > 750 °C
Let's choose the right product for your project together